3.2.12 |
LUNA2 |
Introduction |
| LUNA2 (Linepowered Unit for Network-based Architecture No. 2) is used as the central power supply unit in HiPath 3800. Depending on the system configuration up to three LUNA2 modules can be used in the basic cabinet and up to four LUNA2 modules can be used in the expansion cabinet. |
| When expanding the HiPath 3800 to a two-cabinet system, two LUNA2 modules in the basic cabinet and three LUNA2 modules in the expansion cabinet are enough to supply the maximum configuration in Table 2-26. For information on how to calculate the number of LUNA2 modules required, see Page 3-61. |
| You can use a third LUNA2 in the basic cabinet and a fourth in the expansion cabinet to ensure error-free operation if one LUNA2 module fails (redundant LUNA2) or to charge a connected battery pack or a PowerBox PB3000 (with 4 batteries 12 V/7 Ah). |
|
| LUNA2 supports power supply and battery management functions. No other components are required if it is operated as a power supply. The following options are available for emergency battery operation in the event of a power cut, i.e. the function UPS: |
| • | Connection of battery packs 4 x 12 V/7 Ah (S30122-K5950-Y200) per system cabinet. The batteries are charged via the redundant LUNA2 in the respective system cabinet. Note: Only the S30122-K5950-Y200 battery back is approved for use with LUNA2. |
| • | Connection of the Power Box PB3000 with 4 batteries 12 V/7 Ah (4 x V39113-W5123-E891) per system cabinet. The batteries are charged via the redundant LUNA2 in the respective system cabinet. Note: Only the V39113-W5123-E891 batteries are approved for use with the Power Box PB3000. |
| • | Connection of the Power Box PB3000 with 4 batteries 12 V/7 Ah (4 x V39113-W5123-E891) and LUNA2 as battery charger per HiPath 3800 system. Note: Only the V39113-W5123-E891 batteries are approved for use with the Power Box PB3000. |
| LUNA2 is used in all countries. |
Part numbers |
| • | LUNA2: S30122-K7686-A1, S30122-K7686-M1 For production-related reasons, two different LUNA2 modules with the same functions are used. Technically identical, the two models have minor mechanical differences and are fully compatible with each other. |
| • | Battery pack 4 x 12V/7 Ah: S30122-K5950-Y200 Weight (including batteries): 14.1 kg Dimensions (length x width x height): 280 mm x 160 mm x 140 mm (the connection cable for LUNA2 is part of the battery pack) |
| • | Power Cabinet PB3000 (see Page 9-6) |
Technical Specifications |
| • | Nominal voltage range: 110 Vac - 240 Vac |
| • | Nominal frequency: 50 Hz - 60 Hz |
| • | Output voltage (battery charging voltage, if a LUNA2 is used as a battery charger): -54.7 VDC; -53.5 VDC (for gel cell batteries, currently not released) |
| • | Output current (battery charge current, if a LUNA2 is used as a battery charger): max. 2 A |
| • | Bridging times Table 3-22 lists the maximum possible bridging times (emergency battery operation in case of power failure) with 48-V/7-Ah battery pack (S30122-K5950-Y200), and Powerbox PB3000 (S30177-U773-X). |
Front view of LUNA2 with indicators and switches |
| • | LED for displaying the operating status: |
| - | Illuminated = LUNA2 is operating as power supply unit |
| - | Flashing = LUNA2 is operating as a battery charger |
| - | Off = At least one secondary operating voltage is outside the tolerance zone. In this case a) the voltage feed for LUNA2 may not be sufficient (an additional LUNA2 module is required. For information on how to calculate the number of LUNA2 modules required, see Page 3-61.). b) LUNA2 may be defective (the board must be replaced). |
| • | ON/OFF switch for secondary operating voltages (system supply voltages) |
|
| • | Switches for setting the operating mode (the operating mode must be set before the outer panel is mounted): |
| - | Mode 1: For use as power supply (LED illuminated) |
| - | Mode 2a: For use as battery charger (LED flashing) with a charging voltage of 54.7 VDC |
| - | Mode 2b: For use as battery charger (LED flashing) with a charging voltage of 53.5 VDC |
|
Slots |
| Push the LUNA2 power supply unit into the slots provided in the lower part of the system cabinet shelf until you hear a click (see Figure 4-18). |
| The power supply unit slots must be covered with the outer panel shown in Figure 3-17 (basic cabinet) and in Figure 3-18 (expansion cabinet) before the system is started up. |
Calculating the number of LUNA2 modules required |
| The number of LUNA2 modules required in relation to the number and type of peripheral boards installed can be calculated using the following table. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Examples for a one-cabinet system: |
| a) | Basic cabinet with CBSAP and peripheral boards (without STMI2, SLMA or SLCN) |
| • | A single LUNA2 can supply a CBSAP and up to four peripheral boards. |
| • | A second LUNA2 is required for five or more peripheral boards. |
| • | A third LUNA2 can be used as a battery charger or as a redundant LUNA2. |
| b) | Basic cabinet with CBSAP and peripheral boards (with STMI2, SLMA and/or SLCN) |
| • | Two LUNA2s are always required to supply a CBSAP, peripheral boards and STMI2, SLMA and/or SLCN. |
| • | A third LUNA2 can be used as a battery charger or as a redundant LUNA2. |
| HiPath 3000/5000 V9, Service Documentation, Issue 7 | up ![]() |
|
![]() |
||
| Disclaimer & Copyright | ID: P31003H3590S100017620 | 2012-06-25 |